基于轮胎行业变频调速水泵负荷平衡控制探讨基于轮胎行业变频调速水泵负荷平衡控制探讨 摘要:在轮胎行业,为控制轮胎硫化高温水供水压力波动范围,采纳多台台同型号水泵单独变频控制方式,实验后,在某种情况下易造成其中某台水泵汽化,泵间负荷不平衡。后采纳负荷平衡控制方案,水泵可以自动根据负荷启停,也可手动启停,实现在运行的泵间负荷平衡。 关键词:轮胎硫化高温循环水;压力控制;水泵;负荷平衡控制;变频器;输出频率;首选泵;从泵。 Abstract: in the tire industry, to control the tyre vulcanizing temperature water supply pressure fluctuation range, with many sets of the same model pumps single frequency conversion control mode, after the experiment, in some cases easy to cause some pumps vaporization, load imbalance between pump. After using load balance control scheme, the pump automatically according to load rev. Stop, also can manual start-stop, realize load balance between the running pump. Key words: tire vulcanization temperature circulating water; Pressure control; Water pump; Load balancing control; Frequency converter; Output frequency; The preferred pump; From the pump. 中图分类号:U464.138+.1 文献标识码:A 文章编号:2095-2104(2025)04-0000-00 0、前言 轮胎行业,轮胎硫化高温循环水是重要工艺介质之一,工艺对其压力要求较高,必须控制在标准压力±3%的范围内。轮胎硫化高温循环水的压力,是轮胎硫化工艺控制的重要参数,大规模轮胎生产企业,单台水泵的供水能力常常不能满足生产需求,必须采纳多台水泵并联运行供水。此时,多台水泵并联运行的负荷平衡问题成了供水系统水压控制的难题。 1、高温水压力控制现状分析 目前,对轮胎硫化高温循环水的压力控制有旁路调节、主回路加旁路调节、变频器加水泵软启动器调节等三种。 1)旁路调节是使用最多的一种压力调节方法,其优点是调节系统简单。缺点是:①无论轮胎硫化机开多少台,水泵总处于满负荷运行状态,多余的高温循环水从旁路调节阀泄回去,形成短路循环,造成了不必要的能源浪费;②旁路调节阀反映滞后,压力波动较大,调节水压品质不佳。 2)主回路加旁路调节是针对旁路调节的缺点改...