1 目录 一、现场施工要求······································2 二、设备的摆放·······································2 三、材料的摆放·······································3 四、设备的安装·······································3 -4 五、套管的安装·······································5 六、固定码的安装··································5 ~6 七、冷媒管的安装··································6 ~7 八、排水管的安装··································8 ~9 九、保温作业·····································9 ~1 0 十、试压作业········································1 0 十一、配线作业·······································11 2 一、现场施工要求 1 公司统一的服装; 2 佩戴施工牌; 3 配戴安全帽; 4 张贴现场提示牌; 5 文明施工、安全施工; 二、设备的摆放 1 堆放场所应具备防水、防尘、防晒条件; 2 设备应按外包装标示堆放; 3 室内机堆放的层数,不可超过设备外包装上的标示要求,面板不可超过 2 4 层; 4 设备包装完好; 5 禁止踩踏; 6 设备按外包装标示堆放; 7 室外机堆放的层数不可超过外包装上的标示要求; 8 设备包装完好; 3 三、材料的摆放 1 堆放场所应具备防水、防尘、防晒条件; 2 冷媒管清洁后应做好封口处理; 3 冷媒管离地300m m 以上搁置堆放,并防止碰撞受损; 4 保温材料按型号包装好; 5 保持保温材料内外表面干净清洁; 6 排水管按型号进行堆放; 7 按不同的材料类型、规格分类摆放,标识清楚; 四、设备的安装 室内机安装 1 室内机吊装下方双螺母固定; 2 丝杆不小于Φ10m m (内机用吊耳吊装,不能用拉爆); 3 丝杆要保持垂直; 4 丝杆的长度统一在机器的中间位置; 5 室内机水平安装±1°以内 ; 6 室内机有足够的送回风空间; 7 室内机...