电力工程施工安全操作规程天津市新津建设有限公司2024年9月1日1目 录1、停电作业········································12、带电作业········································23、临时用电········································24、伐树、涉水、履冰··································35、装卸、运输······································66、挖沟、挖坑·······································97、拉线安装······································108、落地式变压器···································109、杆上设备······································1310、现场灌注混凝土································1311、组立杆塔······································1312、放线、紧线·····································1413、高空作业·····································1614、箱式变电所安装································1715、电缆敷设······································18电力工程施工安全操作规程1 停电作业1.1 在带电的杆塔上或带电设备附近作业时,作业人员的活动范围及 其所携带的工具、材料等与带电体的距离小于表 1。1 的规定时应停电 作业。在带电线路杆塔上或带电设备附近作业的安全距离电压等级(kV)安全距离(m)电压等级(w)安全距离(m)10 及以下0.71542.020~35L 02203.060~1101.53304.01。2 停电作业线路与另一带电线路相接近或交叉,工作时可能与带电线路的带电体接触或接近至表 1.2 的安全距离以内,则此带电线路亦 应停电并予接地.接近或交叉其他电力线工作的安全距离电压等级(w)安全距离(m) 电压等级(kV)安全距离(m)10 及以下1.0154~2204.020~352.53305.060~1103.01.3...