钢结构2014年第2期第29卷总第182期某钢结构房屋倒塌事故分析及思考韩建强1谢俐1陈刚2(1.广州市设计院,广州510620;2.广州市第四建筑公司,广州510220)摘要:分析了某二层钢结构房屋倒塌的过程与现状,指出结构设计缺陷是该钢结构房屋倒塌的主要原因。在此基础上,研究消除这些结构设计缺陷对结构性能的改善,并提出柱下梁无支承加劲肋时,梁翼缘最小厚度的计算方法及公式。关键词:房屋倒塌;柱长细比;上下柱不贯通;梁翼缘厚度;梁支承加劲肋;纵向框架梁;结构侧向刚度;施工顺序DOI:10.13206/j.gjg201402011ANALYSISANDINVESTIGATIONONTHECOLLAPSEOFASTEELFRAMINGSTRUCTUREHanJianqiang1XieLi1ChenGang2(1.GuangzhouDesignInstitute,Guangzhou510620,China;2.GuangzhouFourthConstructionCompany,Guangzhou510220,China)ABSTRACT:Thispaperanalyzedthecollapseprocedureandpresentsituationofatwo-storysteelframe,itwasalsopointedoutthatthestructuralcollapseresultedfromtheimproperstructuraldesign.Basedontheanalysis,improvementsonthefailuredesignwereinvestigated,andthecalculationmethodandformulaoftheminimumflangethicknessofthesteelbeamsupportingcolumnwithoutstiffernerwereproposed.KEYWORDS:collapseofbuilding;slendernessratioofcolumn;discontinuouscolumn;flangethickness;stiffernerofbeam;longitudinalframebeam;lateralstiffness;constructionsequence第一作者:韩建强,男,1959年出生,工学博士,教授级高级工程师。Email:hjq333@21cn.com收稿日期:2013-11-071工程概况倒塌的钢结构房屋位于广州市海珠区,为三滘村自建消防站。由于没有结构图纸,所提供的建筑方案图又与现场情况相差甚远,建筑及结构的实际情况只能通过询问当事人及现场实际查勘获得。图1钢柱平面布置示意三滘村自建消防站为二层钢框架结构,采用压型钢板组合楼板。经专家组现场实测,纵向总长度为29.4m,分为7跨,北端第一跨为4.95m,其余跨均为4.05m;横向宽度为8.2m,分为2跨,柱距3.4m,二层和屋面层端部悬挑1.2m。首层高度4.75m,二层高度3.5m,首层面积为205.8m2,二层及屋面面积为241.08m2。基础采用条形基础。钢柱平面布置见图1,二层与屋面层的结构布置见图2,剖面见图3,柱脚大样见图4。主要构件截面及材质如表1所示。注:GL为钢梁编号,GL1尺寸为H250×120×5×8,GL2尺寸为H200×100×4.5×6。a-二层;b-屋面层图2结构平面布置示意84工程设计SteelConstruction.2014(2),Vol.29,No.182a-纵剖面;b-横剖面图3结构剖面示意图4柱脚大样表1构件截面尺寸及材质构件类型截面尺寸/mm材质钢柱H200×100×5×7Q235B二层楼面钢梁H250×125×5×8Q235B屋面钢梁H200×100×4.5×6Q235B二层楼板及屋面板120(压型钢板组合楼板厚)C30/Q2352房屋倒塌事故概述该工程于2012年8月7日开...