Configu re the S7-200 PLC 1
Start Step7-Micro/Win 32
Create a new project or load your existing one (Figure 1 below): FIGURE 1: STEP 7 - MICRO/WIN32 - PROJECT1 DIALOG BOX 2
Click on Tools and then select Ethernet Wizard
Step through the wizard: FIGURE 2: ETHERNET WIZARD 4
Click Yes when asked to use symbolic addressing
Otherwise the wizard cannot continue: FIGURE 3: CLICK YES 5
Enter the module position of the CP243-1
If you are uncertain about the position, click the button Read Modules
Otherwise you can enter the number directly: FIGURE 4: SPECIFY MODULE POSITION DIALOG BOX 6
Enter the IP configuration of your CP243-1
Especially during the startup phase of the project, I would recommend not to use a BOOTP server
Let the module detect the connection type (Figure 5 below): F