施工现场临时用电计算1、总配电室①、总配电室用电量计算:序号机具名称型号额定功率(KW )台数总功率KxCos etgePe=(Jc/Jn1 沪 js=Kx x PeQjs= Pjx tge所属回路1塔吊QTZ63402800.40.61.33101.240.553.9三、五2双笼电梯SCD1/1303900.40.61.333647.9二、三、五3钢筋切断机GJ-50114440.60.71.0226.427四、五4钢筋弯曲机GM -1444160.60.71.029.69.8四、五5钢筋调直机GT4/144280.60.71.024.84.9四6螺纹滚压机HGS62120.60.71.027.27.3五7园盘锯MJ1143260.60.61.023.63.7二、四8单面压刨机MB104A4280.60.61.024.84.9二、四9对焊机UN1 -115010.350.42.2910637.185五10沟通电焊机BX -32641040.350.42.2973.525.758.9二、三、四11振动机ZX501.144.40.60.71.022.62.7二、三、四12高压水泵111110.750.81.028.38.4一13套丝切管机TQ -31110.30.61.020.30.3二14电动弯管机WYQ1.111.10.30.61.020.330.3二15镝灯3.54140.511.177.7二、三、四16碘钨灯115150.511.17.58.3二、三、四17车间照明1550.511.12.52.8二、三、四主体高峰期主要用电负荷:五五五五五18电蒸箱122240.50.91.11213.2一19电饭锅1.5460.50.81.133.3一20冰箱1.534.510.71.14.55一21开水器201200.60.91.11213一22排烟机0.531.50.50.61.10.80.9一23饮水机0.61060.60.91.13.64一24电脑0.3562.10.70.71.11.51.7一25复印机1.211.20.30.81.10.40.4一26打印机0.631.80.20.81.10.40.4一27空调1.520300.60.71.11820一28生活区照明0.14040.611.12.42.6一29电风扇0.06201.20.611.10.70.8一30备用10100.61.166.6小计674.8284.234.4考虑对焊机避开高峰期使用-37.1-85合计244.13315.4Kx —利用系数;Cose 一功率因数;Pjs—有功功率;Qjs—无功功率。总负荷计算,总箱同期第数取 Kx=0.9总的有功功率 Pjs=Kx x£Pjs=0.只 244.13=219.72KVA总的无功功率 Qjs=Kx x£Qjs=0.9x 315.4=283.86 KA总的视在功率 Sis=,Pjs2 Qjs2 = .\,.'219.722 283.86 2 =358. 9 KVA建设方需提供大于 360KV A 以上容量才能满足使用。②、总配电箱进线截面及进线开关选用总的电流计算 Ijs ——Sis一 = ——3589——=545A1.732Ue 1.732 0.38⑴、选择导线截面:选择铝芯塑料绝缘导线 YC -2 (3x 120+2 x 70)。由于距建设方总配电房近,因此无需校核电压降的选择。⑵、选择总进线开关:HSG1 -6/3,额定电流为 6A。2、一回路导线及分配电箱、开关箱内电气设备选择:①、一回路进线及开关选择:电流计...