1目录1、消防控制室管理及应急程序········································22、消防报警信号处置程序·············································33、火灾自动报警系统逻辑关系········································44、消防控制室值班制度················································55、消防水泵房管理制度················································66、消防水泵房启泵流程················································77、防火巡查检查制度···················································88、消防组织结构图······················································99、装修、施工消防管理制度···········································1010、消防设施检查、维修和保养制度··································1211、灭火应急疏散预案··················································1512、用火用电消防安全管理制度·······································1713、消控中心人员岗位职责·············································1914、消防安全责任制度··················································202消防控制室管理及应急程序(一)消防控制室必须实行每日24小时专人值班制度,每班不应少于2人。(二)消防控制室的日常管理应符合《建筑消防设施的维护管理》(GA587)的有关要求。(三)消防控制室应确保火灾自动报警系统和灭火系统处于正常工作状态。(四)消防控制室应确保高位消防水箱、消防水池、气压水罐等消防储水设施水量充足;确保消防泵出水管阀门、自动喷水灭火系统管道上的阀门常开;确保消防水泵、防排烟风机、防火卷帘等消防用电设备的配电柜开关处于自动(接通)位置。(五)接到火灾警报后,消防控制室必须立即以最快方式确认。(六)火灾确认后,消防控制室必须立即将火灾报警联动控制开关转入自动状态(处于自动状态的除外),同时拨打“119”火警电话报警。(七)消防控制室必须立即启动单位内部灭火和应急疏散预案,并应同时报告单位负责人。附件2:3附件3:现场处置通知人员查看各设备运行情况,启动消防广播,协助人员疏散。全部事项处理完毕后,先将所有联动设备复位,再将报警主机复位,并记录备案。故障修复,设备复位,并做好记录火灾自动报警系统主机报警火警:火警指示灯亮,显示火警位置、点位、回路、时间故障:故障指示灯亮,显示故障部位派员或通知人员现场查看确认误报设备复位,并做好记录确认火灾消防报警信号处置程序将火灾报警联动控制开关转入自动状态拨打119启动单位内部灭火和应急疏散预案报告单位负4火灾自动报警系统逻辑关系注:1、火灾确认系指:探测区域内任一手动火灾报警按钮动作,或火灾探测器报警后经人工确认,或同一报警区域两个不同编码的火灾探测器均动作。2、消防控制室应能直接启动下列消防设施:(1)消火栓泵、喷淋泵;(2)送风口、送风机,排烟阀(口)及排烟风机;(3)防火卷帘;(4)消防应急广播(警报装置);(5)其他设施。3、自动喷水灭火系统:报警阀压力开关动作直接连锁自动启动喷淋泵或消防控制室、水泵房直接启动喷淋泵,消防控制中心显示压力开关、水流指示器及喷淋泵动作信号。附件4:火灾报警后中心火灾确认后中心消防控制中心启动本报警区域的排烟阀(口)排烟风...