4 Terminal Filtration 终端过滤器 This level of filtration uses HEPA filters typically at the supply air terminal, and associated with cleanrooms classified as cleaner than ISO 8
A terminal filter may also be used on return/exhaust air when process room air is contaminated with environmentally sensitive particulates (hazardous airborne materials)
These filters should have a silicone gel seal on the downstream side of the filter to form a positive seal to eliminate air bypass around the filter perimeter
Permanent upstream and downstream media protective screens (media guards) should be included to prevent physical damage to the media
Individual HEPA filters in filter banks should be able to be replaced without disruption of adjacent filters
H14 (99
995% @MPPS) efficient filter is recom