目 录一、系统简介..............................................................................................1二、编制依据..............................................................................................3三、调试组织机构......................................................................................5四、调试仪器、设备..................................................................................5五、人员配置..............................................................................................6六、调试准备..............................................................................................6七、系统调试步骤......................................................................................6八、调试内容及方法..................................................................................8九、资料、图纸的收集和整理................................................................22十、环境保护的措施................................................................................23十一、安全保证措施................................................................................24十二、消防记录资料................................................................................26消防系统调试方案一、系统简介本工程消防系统包含六部分:室内消火栓系统,室外消火栓系统,自动喷水灭火系统,七氟丙烷(FM200)气体灭火系统,移动手提灭火器,以及火灾报警系统。1、室内消火栓给水系统 地下二层设 580m3 消防水池,储存室内消火栓系统及自动喷水系统用水量。分为两格,水池为钢筋混凝土水池,并设液位显示器。在主楼屋顶设容积 18m3 不锈钢消防水箱,储存火灾前 10min消防用水量,并由两套独立的稳压装置为室内消火栓及喷淋管网稳压。主楼室内消火栓用水量 40L/s,火灾延续时间 3h。地下二层消防水池储存 3h 室内消火栓水量,室内消火栓管网设置为环状。火灾发生时,由设于消防泵房的二台室内消火栓泵 (一用一备)抽取消防水池的水,经加压后送至室内消火栓环网。系统设计为临时高压系统,管网稳压由屋顶消防水箱维持。水箱的水位由水箱水位仪自动备保持消防管内压力。火灾发生时,通过破玻按...