5 Other Important Items其他重要项目No序号Item项目Item名称Summer Tem 夏季温度(Ԩ) Humidity湿度Winter Tem 冬季温度(Ԩ) Humidity湿度Fresh Air 新风量系统Exhaust Air 排风系统Public Areas, Offices & B.O.H. 23213 6m3/h m2 Main MEP Requirements 酒店主要机电设施要求1 AC and Smoke Exhauting System空调和防排烟系统2 Water and Fire‐fighting System给排水和消防系统3 Electricity System强电系统4 Security, BMS, Accounting, CCTV, Dimming System etc.弱电系统HILTON Requirement希尔顿要求General Requirement 总体要求: Hotel infrastucture must be independent system. Otherwise, hotel must control all main MEP plant rooms and Energy Acounting System have to be installed completely which can separate hotel from non hotel area. 酒店机电系统必须是独立的.否则,酒店必须控制所有的机电主机房并且能源计量系统必须安装完整能够彻底分开酒店和非酒店区域的能源费用.1 AC and Smoke Exhauting System空调和防排烟系统公共区域,办公室和后台区50%40%3.6m3/h.m2Retail Spaces, SnackBars & Pantries 零售店, 甜点吧和操作2350%2140%5.4m3/h.m2Restaurants & FunctionRooms 餐厅和会议室2250%2240%7.2m3/h.m2 6 air changes per hour.Bars, Ballroom & Ballroom Lobby 酒吧,宴会厅和宴会厅前厅2250%2240%9m3/h.m2Guestroom客房 2350%2240%120m3/h.rm Exhaust 102m3/hour through bathroom.Guest Room Corridors 客房走廊2350%2140%2 air changes per hour.Public Toilet 公共卫生间2350%2140%12 air changes per hour.Kitchen 厨房≤29Ԩ≥20ԨLaundry and Valet ≤29Ԩ≥20Ԩ15 to 60 air changes per hour of total exhaust area.Parameter参数的采用1洗衣房air, according to theNo序号Item项目 HILTON Requ irement希尔顿要求Swimming Pool 游泳池≤30Ԩ 60%≥ 26Ԩ 60%Variable with potential for 100% fresh air.M&E Plant and Equipment Room 机电设备房≤38Ԩ≥ 20Ԩ7.2m3/h.m2变配电房换气10‐15次/小时;水泵房;6次/小时;冷冻机房6次/小时;锅炉房6次/小时(事故排风12次/小时);汽车库6次/小时(排烟6次/小时).Team Showers, Toilets and ...