技术与应用一起接地变保护动作跳闸原因的分析卢纯义张良杨金飞(金华电业局,浙江金华321001)摘要由于接地变中性点避雷器击穿,使lOkV系统由中性点经消弧线圈接地系统变为中性点经小电阻接地系统
当10kV系统发生B相接地故障时,虽然故障点不在接地变,但接地变A,C相电流互感器测得很大的电流,超过过流I段定值,使接地变跳开
本文对保护动作的原因及故障点进行了分析,并提出了相关的解决对策
关键词:接地变;避雷器;中性点经小电阻接地AnalysisonaRelayActionofEarthedTransformerLuChunyiZhangLiang砀愕Jinfei(JinhuaElectricPowerBureau,Jinhua,Zhejiang321001)AbstractForthebreakthroughoftheneutralarresteroftheearthedtransformer,the1OkVsystembecomesfromthearcsuppressioncoilneutralgroundingsystemtothelowresistanceneutralgroundingsystem.WhiletheBphaseofthe10kVsystemisundertheearthfault.althoughthefaultpointisnotontheearthedtransformer,thetestingcurrentofthecurrenttransformeronAandCphaseiSmuchgreaterthanthevalueofthesectionI.SOtheearthedtransformerwillaction.Thispaperanalysisthereasonsoftheprotectionactionandthefaultpoints