六安医院空调系统设计分析六安医院空调系统设计分析 【摘要】门诊、病房部分的空调系统形式采纳多联式分体空调与单侧大温差水冷式冷水机组结合使用, 门诊、医疗设备用房设置多联式空调机组,根据各科室的运行时间及使用情况分区独立控制。病房区域冷、热负荷相对稳定,即用较为集中的风机盘管系统。建筑物内的新风系统均由新风机组提供。 【Abstract】 Outpatient wards, part of the air conditioning system use multiple split type air conditioner and Unilateral large temperature difference water cooled chiller combination, outpatient、medical equipment room set of multiple air-conditioning unit, according to the various sections of the running time and the use of independent zoning control。Ward area of cold and heat load are relatively stable, use relatively centralized fan-coil unit system。Buildings by the fresh air unit with fresh air system。 【关键词】 多联机空调 变制冷剂空调 单侧大温差冷水机组 分区独立控制 净化空调系统 【Keywords】 multiple split type air conditionerVariable refrigerant air conditioning Unilateral large temperature difference water chiller Independent zoning controlHVAC Heating Ventilation Air Conditioning 中图分类号:S611 文献标识码:A 文章编号: 1 引言 六安市人民医院位于安徽省六安市,建筑面积 60471m2,地上十七层,地下一层。此次设计的为医院的综合楼,楼内包含地下平常车库、设备用房、地上门诊,医技房间、手术室和病房,车库部分战时为二等人员掩蔽所。制冷机房设置在地下一层车库外的区域,机房面积 290m2 。多联式空调系统的室外机放置在五层屋面上,此屋面场地开阔,室外机可以靠近内侧放置,不影响外立面的建筑效果,而且还可以保证多联式空调机组室外机的通风效果。多联式空调室内机每层按科室设置,每个科室的空调系统可以单独控制,方便使用,也有利于医院科室的单独计量。手术室等干净空调系统仍采纳水冷式冷水机组供冷,水管为四管制。病房采纳风机盘管加新风系统,冷源由制冷机房提供。 2 空调系统设计方案的分析 2.1 设计参数及概况 六安市在省会合肥的西侧,距离合肥市约 100 公里,属于夏热冬...