漏电开关模拟试验记录 表C6-36 编 号 06-C6-001 工程名称 行政司楼维修改造工程 试验器具 漏电流测试器 试验日期 2009-10-28 安装部位 型号 设计要求 实际测试 动作电流 (mA) 动作时间 (mS) 动作电流 (mA) 动作时间 (mS) B1AL1 C65N-C/2P+Vigi20A,30m A ≤30 ≤100 26 80 B1AL1 C65N-C/2P+Vigi16A,30m A ≤30 ≤100 26 90 B1AL2 C65N-C/2P+Vigi16A,30m A ≤30 ≤100 26 89 B1AL3 C65N-C/2P+Vigi20A,30m A ≤30 ≤100 26 97 B1AL3 C65N-C/2P+Vigi16A,30m A ≤30 ≤100 26 98 B1AL4 C65N-C/2P+Vigi20A,30m A ≤30 ≤100 26 85 B1AL4 C65N-C/2P+Vigi16A,30m A ≤30 ≤100 26 86 B1AL5 C65N-C/2P+Vigi16A,30m A ≤30 ≤100 26 82 B1AL6 C65N-C/2P+Vigi16A,30m A ≤30 ≤100 26 90 B1AL6 C65N-C/2P+Vigi16A,30m A ≤30 ≤100 26 97 B1AL6 C65N-C/2P+Vigi16A,30m A ≤30 ≤100 26 96 B1AL7 C65N-C/2P+Vigi16A,30m A ≤30 ≤100 26 93 B1AL7 C65N-C/2P+Vigi16A,30m A ≤30 ≤100 26 93 B1AL7 C65N-C/2P+Vigi16A,30m A ≤30 ≤100 26 95 1AL1 C65N-C/2P+Vigi20A,30m A ≤30 ≤10