下载后可任意编辑 SPECIFICATION FOR 6000T/Y VISCIDITY STABLE FIBER PROJECTPROCESS & UTILITY PIPINGSHOT INSULATION REQUIREMENTSThe attached specification ,revised as indicated below,is issued herewith. If this is a later revision thannow in your possession,please destroy previous issue.Rev 0 Date 04-06-07 By App Cust App PageRev Date 04-06-07 By App Cust App PageRev Date 04-06-07 By App Cust App PageRev Date 04-06-07 By App Cust App PageRev Date 04-06-07 By App Cust App PageNote:New issue …………………………………………… Revised sheets only attachde …………………… Entire specification reissued …………………… 保 温 施 工 规 范 (附件2)1.0 适用范围----------------------------精品 word 文档 值得下载 值得拥有---------------------------------------------------------------------------------------------------------------------------------------------------------------------------下载后可任意编辑本规定适用于管线、塔槽、及设备,其操作温度在60℃以上,650℃以下时外部热保温的材料以及使用方法.2.0 一般设计法律规范 2.1 塔槽、设备及管线的保温度依据厚度表决定之.需要热追踪的管线,除非施工图上有其它注明,否则其保温厚度仍然不变.当操作温度超出保温厚度表内所列温度时,保温的厚度及使用另须依照合约上的规定. 2.2 本法律规范内的保温材料,适用于操作温度在60℃至650℃之间.2.3 管线、塔槽或换热器,须先按“油漆施工法律规范”做好除锈油底漆工作.其表面如附有油脂、浮灰、污物或水汽湿气时,须处理洁净后,始得保温. 2.4 管线、塔槽及设备操作温度在60℃至650℃之间,基于制程需要“温度控制”或为“保护现场工作人员的安全”,则需保温.2.5 泵浦和透平机除非需温度控制,否则不需保温。2.6 管线操作温度超过80℃时,必须在操作人员接近的区域作人员安全保温,安全保温的范围以不超过操作台6尺高或2尺宽的范围为原则.阀类、法兰、由任除非特别注明,否则不需做安全保温.保温设施要求的程度,在施工图中会有所指示,假如有其它有用的保护或遮蔽设施,能保护操作人员的安全,也可以用来代替安全保温.----------------------------精品 word 文档 值得下载 值得拥有-...