漏电开关模拟试验记录表C6-36编号06-C6-001工程名称行政司楼维修改造工程试验器具漏电流测试器试验日期2009-10-28安装部位型号设计要求实际测试动作电流(mA)动作时间(mS)动作电流(mA)动作时间(mS)B1AL1C65N-C/2P+Vigi20A,30mA≤30≤1002680B1AL1C65N-C/2P+Vigi16A,30mA≤30≤1002690B1AL2C65N-C/2P+Vigi16A,30mA≤30≤1002689B1AL3C65N-C/2P+Vigi20A,30mA≤30≤1002697B1AL3C65N-C/2P+Vigi16A,30mA≤30≤1002698B1AL4C65N-C/2P+Vigi20A,30mA≤30≤1002685B1AL4C65N-C/2P+Vigi16A,30mA≤30≤1002686B1AL5C65N-C/2P+Vigi16A,30mA≤30≤1002682B1AL6C65N-C/2P+Vigi16A,30mA≤30≤1002690B1AL6C65N-C/2P+Vigi16A,30mA≤30≤1002697B1AL6C65N-C/2P+Vigi16A,30mA≤30≤1002696B1AL7C65N-C/2P+Vigi16A,30mA≤30≤1002693B1AL7C65N-C/2P+Vigi16A,30mA≤30≤1002693B1AL7C65N-C/2P+Vigi16A,30mA≤30≤10026951AL1C65N-C/2P+Vigi20A,30mA≤30≤10026851AL1C65N-C/2P+Vigi16A,30mA≤30≤1002691测试结论经对配电箱内漏电开关测试,所有漏电保护装置的动作电流和动作时间均符合设计及施工验收规范。签字栏建设(监理)单位施工单位北京城建亚泰建筑装饰分公司专业技术负责人专业质检员专业工长本表由施工单位填写,建设单位、施工单位各保存一份。漏电开关模拟试验记录表C6-36编号06-C6-002工程名称行政司楼维修改造工程试验器具漏电流测试器试验日期2009-10-28安装部位型号设计要求实际测试动作电流(mA)动作时间(mS)动作电流(mA)动作时间(mS)1AL1C65N-C/2P+Vigi16A,30mA≤30≤10026821AL1C65N-C/2P+Vigi16A,30mA≤30≤10026901AL1C65N-C/2P+Vigi16A,30mA≤30≤10026991AL1C65N-C/2P+Vigi16A,30mA≤30≤10026971AL1C65N-C/2P+Vigi16A,30mA≤30≤10026981AL2C65N-C/2P+Vigi20A,30mA≤30≤10026841AL2C65N-C/2P+Vigi16A,30mA≤30≤10026861AL2C65N-C/2P+Vigi16A,30mA≤30≤10026831AL2C65N-C/2P+Vigi16A,30mA≤30≤10026901AL2C65N-C/2P+Vigi16A,30mA≤30≤10026971AL3C65N-C/2P+Vigi20A,30mA≤30≤10026961AL3C65N-C/2P+Vigi16A,30mA≤30≤10026951AL3C65N-C/2P+Vigi16A,30mA≤30≤10026931AL3C65N-C/2P+Vigi16A,30mA≤30≤10026951AL3C65N-C/2P+Vigi16A,30mA≤30≤10026861AL3C65N-C/2P+Vigi16A,30mA≤30≤1002691测试结论经对配电箱内漏电开关测试,所有漏电保护装置的动作电流和动作时间均符合设计及施工验收规范。签字栏建设(监理)单位施工单位北京城建亚泰建筑装饰分公司专业技术负责人专业质检员专业工长本表由施工单位填写,建设单位、施工单位各保存一份。漏电开关模拟试验记录表C6-36编号06-C6-003工程名称行政司楼维修改造工程试验器具漏电流测试器试验日期2009-10-28安装部位型号设计要求实际测试动作电流(mA)动作时间(mS)动作电流(mA)动作时间(mS)1AL4C65N-C/2P+Vigi20A,30mA≤30≤10026801AL4C65N-C/2P+Vigi16A,30mA≤30≤10026951AL4C65N-C/2P+Vigi16A,30mA≤30≤10026991AL4C65N-C/2P+Vigi16A,30mA≤30≤10026971AL4C65N-C/2P+Vigi16A,30mA≤30≤10026981AL4C65N-C/2P+Vigi16A,30mA≤30≤10026851AL4C65N-C/2P+Vigi16A,30mA≤30≤10026862AL1C65N-C/2P+Vigi20A,30mA≤30≤10026832AL1C65N-C/2P+Vigi16A,30mA≤30≤10026942AL1C65N-C/2P+Vigi16A,30mA≤30≤10026972AL1C65N-C/2P+Vigi16A,30mA≤30≤10026962AL1C65N-C/2P+Vigi16A,30mA≤30≤10026932AL1C65N-C/2P+Vigi16A,30mA≤30≤10026952AL2C65N-C/2P+Vigi20A,30mA≤30≤10026952AL2C65N-C/2P+Vigi16A,30mA≤30≤10026852AL2C65N-C/2P+Vigi16A,30mA≤30≤1002695测试结论经对配电箱内漏电开关测试,所有漏电保护装置的动作电流和动作时间均符合设计及施工验收规范。签字栏建设(监理)单位施工单位北京城建亚泰建筑装饰分公司专业技术负责人专业质检员专业工长本表由施工单位填写,建设单位、施工单位各保存一份。漏电开关模拟试验记录表C6-36编号06-C6-004工程名称行政司楼维修改造工程试验器具漏电流测试器试验日期2009-10-28安装部位型号设计要求实际测试动作电流(mA)动作时间(mS)动作电流(...