目录第一章 110KV GIS 设备检修规程.........................................21.设备关键配置及技术参数...........................................21.1 ZF28A-145 GIS 基础参数表........................................21.2 断路器基础参数表...............................................21.3 隔离-接地三位置开关基础参数表.................................31.4 接地开关基础参数表..............................................41.5 快速故障关合接地开关基础参数表.................................51.6 电压互感器基础参数表...........................................51.7 电流互感器基础参数表...........................................61.7 电流互感器基础参数表...........................................72.法律规范性引用文件...............................................73.检修分类.........................................................83.1.大修...........................................................83.2.小修...........................................................83.3.临时性检修.....................................................84.检修周期和检修项目...............................................84.1 检修间隔及检修停用时间确实定...................................84.2 检修前准备.....................................................94.3 检修前检验和试验..............................................104.4 检修项目.......................................................105.检修工艺步骤及标准...............................................126.修后试验项目.....................................................13第一章 110kV GIS 设备检修规程1.设备关键配置及技术参数1.1 ZF28A-145 GIS 基础参数表GIS 整体设备设备编号设备型号ZF28A-145额定电压145kV额定电流3150A额定短路开断电流40kA额定短时耐受电流40kA额定短时连续电流4s额定峰值耐受电流100kASF6 气体年漏气率≤0.5%额定短时工频耐受电压(1min)相对地断口间275 kV275+84 kV额定雷电冲击耐受电压相对地断口间650 kV650+118 kV额定 SF6 气体压力(20℃)(MPa)额定压力报警压力闭锁压力断路器气室0.580.530.5其它气室0.580.530.5局部放...