电能质量在线监测装置试验报告铭牌:名称PQM303电能质量在线监测装置型号UK-5508生产厂家金智科技股份二、试验结果:试验日期:2024.03.21温度:20℃湿度:35%一、频率(输入电压57.74V,允许误差0.01Hz)二、 基波电压(允许误差0.2%)标称值( Hz)49.6049.8050.0050.2050.40实测值( Hz)49.60049.80050.00050.20050.400误差(%)0.00000.00000.00000.00000.0000 电压设定(v)55.0057.7460.00实测值(V)误差(%)实测值(V)误差(%)实测值(V)误差(%)A55.030.054557.770,052060.030.0500B55.030.054557.770.052060.030.0500C55.050.090957.790.086660.050.0833 电压设定(v)95.00100.00105.00实测值(V)误差(%)实测值(V)误差(%)实测值(V)误差(%)A95.060.0632100.040.0400105.060.0571B95.050.0526100.030.0300105.060.0571C95.090.094799.900.1000105.090.0857 三、 基波电流(允许误差 0.5%)四、电压不平衡度(允许绝对误差0.2%)电压不平衡度设定测得值(%)误差(%)A相设值B相设值C相设值目标值(%)57.0V, 0° 58.5V,-115°56.7V, 125°2.0382.061.079557.8V, 0°56.45V,-125°59.55V,110°4.0654.050.3690五、电流不平衡度(允许绝对误差1.0%)电流不平衡度设定测得值(%)误差(%)A相设值B相设值C相设值目标值(%)4.9A, 0°5.54A,-127°4.43A, 115°10.009.990.01002A, 0°2A,-135°1A,98°30.0630.130.2329六、谐波电压基波电压: UN=57.74V50Hz谐波含量设定(Uh=0.5%UN, A级允许误差 0.05%UN)电流设定(A)0.501.002.003.005.00实测値(A)误差(%) 实测值(A)误差(%) 实测值(A)误差(%)实测值(A)误差(%)实测值(A)误差(%)A0.500 0.0000 1.000 0.0000 2.000 0.0000 3.0000.00004.9990.0200B0.500 0.0000 1.000 0.0000 2.000 0.0000 3.0000.00005.0000.0000C0.500 0.0000 1.000 0.0000 2.000 0.0000 2.999 0.03334.9990.0200谐波A相测量值B相测量值C相测量值误差(%)误差(%)误差(%)次数2(%)0.500.00000.500.00000.500.00003(%)0.500.00000.500.00000.500.00004(%)0.500.00000.500.00000.500.00005(%)0.500.00000.500.00000.500.00006(%)0.500.00000.500.00000.500.00007(%)0.500.00000,500.00000.500.00008(%)0.500.00000.500.00000.500.00009(%)0.500.00000.500.00000.500.000010(%)0.500.00000.500.00000.500.000011(%)0.500.00000.500.00000.500.000012(%)0.500.00000.500.00000.500.0000l3(%)0.500.00000.500.000...